ENPLRU

Enquiries:

Call: Telefon +48 32 225 88 81

You are here: HomeWet cooling towers

Bora 1600 wet cooling tower

Technical Specifications

Dimensions

1900x1900x3980 mm

Modular dimensions

1600 x1600mm

Fan diameter

900 mm

Hydraulic load

15-50 m3/h

Heat output

up to 900 kW

Weight

572 kg

Used motors

3 KW; 4 KW

Storage capacity

FK19
1200 mm, PP

Degree of protection

IP 56

Additional Information

Inlet connection: DN 100 PN10

PVC material

Outlet connection: DN 100 PN10

Fan system

Fan

WO 900/9-9/40/B/PPG (3kW)

WO 900/9-9/45/B/PPG (4kW)

Air Flow

Q = 7m3/s

Q = 7,5m3/s

Static pressure

ΔPst = 150 Pa

ΔPst = 175 Pa

Air Density

p = 1,12 kg/m3

p = 1,12 kg/m3

Sound pressure level (1m from the diffuser)

LA =82+/-3 dB(A)

LA =82+/-3 dB(A)

Engine information

Type

Siemens

Supply Voltage

U = 400V

Frequency

f = 50Hz

Case Type/protection

IM 3011(V1)/ IP 56

Insulation class

F

Completely assembled compact cooling tower ready to be used

The supporting structure of the cooling tower is made of stainless steel (0H18N9).
Walls, diffuser and basin are made of glass-polyester laminate.
Torsion elements made of A2 steel.