ENPLRU

Enquiries:

Call: Telefon +48 32 225 88 81

You are here: HomeWet cooling towers

Bora 2400 wet cooling tower

Technical Specifications

Dimensions

2410x2410x4525 mm

Modular dimensions

2400 x 2400mm

Fan diameter

1400 mm

Hydraulic load

50-100 m3/h

Heat output

up to 1700 kW

Weight

1256 kg

Used motors

4KW; 5,5 KW; 7,5 KW

Storage capacity

FK19 1200 mm, PP

Degree of protection

IP 56

Additional Information

Inlet connection: DN 150 PN10

PVC material

Outlet connection: DN 150 PN10

Fan system

Fan

WO 1400 - 4 - (7)

Air Flow

Q = up to 18m3/s

Static pressure

ΔPst = up to 180 Pa

Air Density

p = 1,12 kg/m3

Sound pressure level (1m from the diffuser)

LA =82+/-3 dB(A)

Engine information

Type

Siemens

Supply Voltage

U = 400V

Frequency

f = 50Hz

Case Type/protection

IM 3011(V1)/ IP 56

Insulation class

F

Completely assembled compact cooling tower ready to be used